Isolation Signal Splitter D6N 21000
Conversion, Isolation and Distribution of Standard Signals
With the Isolation Signal Splitter D6N 21000 DRAGO is extending its offer on high-functional and high-reliable components of the interface technique.
- Calibrated signal setting
Input and output range can be set by using DIP switch - without any further adjustment - 4-Port isolation
Protection against erroneous measurements due to parasitic voltages or ground loops - Extremely slim design
6.0 mm small housing with practical pull-spring clamps - Protective Separation acc. to EN61140
Protects service personnel and downstream devices against impermissibly high voltage - Maximum reliability
No maintenance costs - 5 Years Warranty
The Isolation Signal Splitter D6N 21000 is used for isolation, conversion and distribution of 0/4...20 mA, 0/1...5 V and 0/2...10 V standard signals. The input and two outputs each can be separately configured. The signal combination is selectable by DIP switch. Its high level of reliability and extremely slim form make the D6N 21000 the first choice in its class!
The Protective Separation with high isolation level provides protection for personnel and downstream devices against impermissibly high voltage and make the D6N 21000 universally applicable for all measurement and industrial applications.
Pluggable cross-connectors for the auxiliary power supply ensures fast and economical installation. The slim housing with 6.0 mm wide saves significant space on DIN-rail in the switch cabinet.
The optimized efficiency of the D6N 21000 power pack contributes significantly to reducing the units own heat generation. This is reflected in extremely high MTBF, it means highest reliability and long-term stability. A green LED on the front of the unit has been provided to monitor the power supply.
Product line
Device | Order No. |
---|---|
Isolation Signal Splitter, calibrated range selection | D6N 21000 |
Device | Order No. | |||
---|---|---|---|---|
D6N 21005 - | X | X | X | |
Input: 0 ... 20 mA | 0 | |||
Input: 4 ... 20 mA | 1 | |||
Input: 0 ... 5 V | 2 | |||
Input: 0 ... 10 V | 3 | |||
Input: 1 ... 5 V | 4 | |||
Input: 2 ... 10 V | 5 | |||
Output I: 0 ... 20 mA | 0 | |||
Output I: 4 ... 20 mA | 1 | |||
Output II: 0 ... 20 mA | 0 | |||
Output II: 4 ... 20 mA | 1 |
(Factory default setting, reconfigurable any time by using DIP-switch)
Data sheet archive:
The products are no longer available!
Technical Data
Input
Input signal | 0...20 mA, 4...20 mA 0...5 V, 0...10 V, 1...5 V, 2...10 V see order information |
|
Input resistance | Current input Voltage input |
≤ 50 Ohm ≥ 100 kOhm |
Overload | Current input Voltage input |
≤ 50 mA ≤ 30 V |
Output I + II
Output signal | 0...20 mA, 4...20 mA see order information |
Load | ≤ 10 V (2x 300 Ohm at 20 mA) |
Offset | < 20 µA |
Ripple | < 10 mVeff |
General Data
Transmission error | < 0,1 % of final value | |
Temperature coefficient 1) | < 100 ppm/K | |
Cut-off frequency | 1 kHz, switchable to 100 Hz | |
Response time (T10-90) | < 300 µs, switchable to < 3,5 ms | |
Test voltage | 2,5 kV, 50 Hz between all circuits | |
Working voltage 2) (Basic Insulation) |
Up to 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits. |
|
Protection against electrical shock | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. |
|
Ambient temperature | Operation Transport and storage |
–25 °C to +70 °C –40 °C to +85 °C |
Power supply | 24 V DC 16,8 V ... 31,2 V DC, ca. 1,0 W | |
EMC 3) | EN 61326-1 | |
Construction | 6.0 mm housing, protection class: IP 20 | |
Weight | Approx. 50 g |
Bold: Factory setting for D6N 21000
- Average TC based on the final value in specified operating temperature range
- As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
- Minor deviations possible during interference
Block diagram

Dimensions

Terminal assignments
- 1 + Input
- 2 − Input
- 3 + Output II
- 4 − Output II
- 5 + Output I
- 6 − Output I
- 7 + Power supply 24 V DC
- 8 − Power supply 24 V DC
Connections
Pull-spring clamps, wire cross-section max. 2.5 mm², stripped length 9...10 mm