- DG 3202
- DG 3282
- DG3202
- DG3282
Limit Value Monitor DG 3202 / DG 3282
Monitoring of Standard Signals with 2 Switching Outputs
The Limit Value Monitors DG 3202 und DG 3282 are used to monitor measured values in 0(4) ... 20 mA and 0 ... 10 V standard signal circuits. A transmitter supply +Us is provided for the operation of 2-wire transmitters.
- Easy configuration on front panel
Operating mode switchable via DIP switch, switch point and hysteresis adjustable with potentiometer - Status indication by LED
Easy monitoring and switching point adjustment - Relay changeover contacts with high power handling
or fully isolated transistor switching outputs - True 4-port separation
Protection against erroneous measurements due to parasitic voltages or ground loops - Protective Separation acc. to EN 61010
Protects service personnel and downstream devices against impermissibly high voltage - High reliability and noise immunity
No microprocessor, no integrated software - Extremely slim design
12.5 mm slim housing for a simple and space saving DIN rail mounting - 5 Years Warranty
Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant
Two switching outputs can be configured simultaneously or independently of each other with the analog control electronics as MIN or MAX alarm in open-circuit or closed-circuit operation.
All setting elements are located behind the openable front cover and can also be operated when the unit is mounted. The switching points and the switching hysteresis can be adjusted with potentiometers. The monitoring states are indicated by yellow LEDs.
Two relay changeover contacts are available on the DG 3202. The DG 3282 is equipped with two isolated transistor switching contacts (open-collector), which can optionally work with pull-up resistors. Input, power supply and the outputs are safely galvanically isolated from each other.
The Protective Separation and the 24 V DC power supply make the DG 3202 and DG 3282 universally applicable for all measurement and industrial applications, as well as for building automation.
Product line
Device | Order No. |
---|---|
Limit Value Monitor with relay contacts | DG 3202 |
Limit Value Monitor with transistor switches | DG 3282 |
Downloads / Links
Technical Data
Input
Input signal | 0(4) ... 20 mA | 0 ... 10 V |
Input resistance | Current input approx. 5 Ω | Voltage input approx. 120 kΩ |
Overload max. | Current input 200 mA | Voltage input 300 V |
Transmitter supply +Us | 16 V at UPower = 24 V, (13 V … 22 V depending on the supply voltage) current limited ≤ 30 mA |
|
Switch point setting | 0 to 110 % with 12-turn potentiometer, independently adjustable for each switching output | |
Hysteresis setting | 0 to 6 % or 0 to 60 % of measuring range switchable, adjustable with potentiometer |
Output
DG 3202 (Relay): | |
Contact type | 2 changeover relays (SPDT) |
Switching capability AC max. | 250 V / 6 A, 1500 VA |
Switching capability DC max. | 250 V / 0.2 A, 115 V / 0.3 A, 30 V / 6 A Recommended minimum load 300 mW / 5 V / 5 mA |
DG 3282 (Transistors): | |
Contact type | 2 transistor switches, fully isolated, optional 10 kΩ Pull-up resistor |
Switching capability | 30 V DC, max. 50 mA, residual voltage < 1.5 V, not current limited |
Status indication | one yellow LED per switching output |
Response time | approx. 20 ms |
General Data
Switch error | < 0.2 % full scale | |
Temperature coefficient 1) | < 150 ppm/K | |
Test voltage | 4 kV, 50 Hz, 1 min. input against power supply against both switching outputs 3 kV, 50 Hz, 1 min. switching output 1 against switching output 2 |
|
Working voltage 2) (Basic Insulation) |
1000 V AC/DC for overvoltage category II and 600 V AC/DC for overvoltage category III acc. to EN 61010 and pollution degree 2 between input, power supply and both switching outputs. Furthermore 300 V AC/DC between output 1 and output 2. | |
Protection against electrical shock 2) | Protective separation according to DIN EN 61140 by reinforced insulation according to DIN EN 61010 up to 600 V AC/DC at overvoltage category II and 300 V AC/DC at overvoltage category III at pollution degree 2 between input, power supply and both switching outputs. Furthermore 300 V AC/DC between output 1 and output 2. | |
Power supply | 24 V DC, ± 15 %, approx. 1.0 W | |
Ambient temperature | Operation Transport and storage |
–20 °C to +60 °C (-4 to +140 °F) –35 °C to +85 °C (-31 to +185 °F) |
EMC 3) | EN 61326 -1 | |
MTBF (acc. to EN 61709 / SN 29500) | 575.4 years (Tamb. 40 °C, FIT 198) | |
Construction | 12.5 mm (0.5") housing, protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715 | |
Connection | Captive plus-minus clamp screws, Wire cross-section max. 2.5 mm² / AWG 14 Stripped length 6 … 8 mm / 0.28 in, Screw terminal torque 0.8 Nm / 7 lbf in |
|
Weight | 70 g |
- Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
- For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
- Minor deviations possible during interference
Block diagram
Dimensions
Terminal assignments
- 1.1 + Power supply +
- 1.2 − Power supply −
- 2.2 + +Us
- 2.1 + Voltage Input +
- 3.1 + Current Input +
- 3.2 − Input −
- Output 1
- 4.1 COM Out+
- 4.2 NO Out−
- 5.1 NC Pull-Up
- Output 2
- 6.1 COM Out+
- 6.2 NO Out−
- 5.2 NC Pull-Up
Subject to change!